Engineering via SICAM WEB
Halt program
Precondition: The application program is running in normal mode.
When clicking on the button
and the test mode is automatically switched on.
This is displayed as follows:
The buttons are enabled/blocked as follows:
Run Single Program Cycle
Precondition: The application program is halted.
When clicking the button
cycle and is halted again.
The status display of the application program and the buttons do not change.
With this function you can trace for instance the status change of variables for each program
cycle, or change the value of a signal input for exactly 1 program cycle.
Continue Program Processing
Precondition: The application program is halted.
When clicking the button
test mode remains switched on.
This status changes as follows:
The buttons are enabled/blocked as follows:
256
, the cyclic processing of the application program is halted
(Cycle step), the application program executes only one single
, the application program is processed cyclically again and the
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016