5.1.9.4.1 Automatic Display of Signal States

Process signals that are acquired or output via HW pins are automatically configured for the
process display via SICAM WEB and for the process display on the LCD.
The automatic process display resides in SICAM WEB in the menu I/O Modules (see
5.1.10.2,
Display Process
The automatic process display resides on the LCD in the menu Monitoring | I/O Modules
(see 6.1.2.4.6,

5.1.9.4.2 Parameters with Assignment on the DI Module

Processing type
DI_DI – double-point in-
formation input
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
Values).
I/O
Modules).
Parameter
Inversion_0
Flutt_dp_qds
Inversion_1
block
SVM_monitoring
Flutt_Number
SW_Filter_t
Flutt_t
int_posit_t
faulty_pos_t
AR_sign_t
ON_before_OFF
Moduleselection_SVM_
monitoring
Flutt_t_stable
Engineering via SICAM WEB
Meaning
Inversion (S)
NO/YES
Datapoint quality discriptor for fluttery binary
information
BL/IV
Inversion (S)
NO/YES
Blocking (=not used) (S)
NO/YES
Power monitoring. The sensor voltage is moni-
tored by an own power monitoring input (S).
NO/YES
Number of transients for flutter suppression
(S)
Software filter-time in s (S)
Flutter time in seconds.
0 = no fluttersuppression (S)
0.1 to 6553.5
Intermediate position suppression time in se-
conds.
0 = no intermediate position suppression (S)
Faulty position suppression time in seconds.
0 = no faulty position suppression (S)
Time for signalling the automatic reclosure in
seconds 0=no signalling of autom. reclosure
(S)
0.1 to 25.5
Definition of the order for the wiring of double
commands/double point information NO: OFF
is I/O with lower I/O number ON is I/O with
higher I/O number YES: ON is I/O with lower
I/O number OFF is I/O with higher I/O number
NO/YES
Switch for power monitoring handling (PM)
Standard PM (PM inputs per modules) or input
IN D17 of one BI-module as PM input for all
modules Attention: Selected module must be
a DI module.
Flutter suppression: stability time in seconds.
0 = stability time defined through parameter
Flutt_t (S)
0.1 to 6553.5