5.1.9.4.4 Parameters with Assignment on the AI Module

Processing type
AI_I – current value
acqisition
204
Parameter
line frequency
Zero range
thresh_additive
thresh_uncond
block
Processing grid
X_0%
X_100%
Y_0%
Y_100%
Smoothing
MV_conv_free_Xl
zero_range_Xzu
zero_range_Xzl
zero_range_Yz
zero_range_a MV_conv
OV_suppr_t
Meaning
The noise rejection takes place for the
parametrized line frequency
· 50 Hz
· 60 Hz
· 16.7 Hz
Zero range suppression (and check of the
plausibility limits) (S)
NO/YES
Change threshold in % of X_100% (S) AI_T:
% of temperature range
0 to 1000.0
Change threshold in % of X_100% (S) AI_T:
% of temperature range
0 to 103.00
Blocking (=not used) (S)
NO/YES
Processing grid in seconds
0.1 to 25.5
Nominal range in the physical unit of the in-
put/output (0%) (S)
-50.0 to 50.0
Nominal range in the physical unit of the in-
put/output (100%)
-50.0 to 50.0
Technological or normalized value 0% (S)
-1000000000000000.000 to
1000000000000000.000
Technological or normalized value 100% (S)
-1000000000000000.000 to
1000000000000000.000
0 - 99 in %. 0% = no smoothing, 99% = high-
est possible smoothing
0 to 99
Limit of not plausible range. Parameter is only
effective, if the parameter ze-
ro_range_a_MV_conv is set to free
parametrizable (in the physical unit of the in-
put) (S)
-103.00 to 103.00
upper limit of zero range in % of X_100% (S)
-103.00 to 103.00
lower limit of zero range in % of X_100% (S)
-103.00 to 103.00
Technological or normalized value of zero
range (S)
-1000000000000000.000 to
1000000000000000.000
Zero range suppression (and check of the
plausibility limits) either standard or free
parametrizable (S)
· standard
· free configurable
OV suppression time in seconds, 0=no OV
suppression
0 to 255
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016

Advertisement

Table of Contents
loading

Table of Contents