Siemens SICAM CMIC User Manual page 219

Remote terminal units
Table of Contents

Advertisement

Type
Double information to double command
(2-pole):
DI-810x with DO-820x
Double information to double command
(2-pole):
DI-811x with DO-821x
(2 DO-821x mit 1 DI-811x possible)
x = 0..7, y = x+1, z = x+2
Note
In each case the module DO-62xx must be equipped directly after the module DI-610x.
Checked Command Output
For the output of checked commands the corresponding digital output modules must be
equipped and the DO signals to be used must be configured.
Parameters are set only on the command output relay module.
You find the exact information on the checked command output in the manual SICAM RTUs
Common Functions Peripheral Elements According to IEC 60870-5-101/104, chapter "Pulse
Commands", section "Functions Dependent on the Hardware of the System Element".
Required I/O modules:
·
1 command output basic module, alternatively
─ DO-6220 – command output with internal checks IC1
─ DO-6221 – command output with resistance check RC1
·
1 up to 5 command output relay modules DO-6230, alternatively
─ 8 relay outputs for 16 pulse commands with 1- or 1.5-pole wiring
─ 8 pulse commands with 2-pole wiring
Note
A mixed wiring (1-, 1.5- and 2-pole) on one module DO-6230 is not permissible. For varied wirings addi-
tional DO-6230 must be used.
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
Predefined Assignment
DM IOM x – IN D00/D01 ... command IOM y – OUT D00..D03
DM IOM x – IN D04/D05 ... command IOM y – OUT D04..D07
DM IOM x – IN D00/D01 ... command IOM y – OUT D00..D03
DM IOM x – IN D04/D05 ... command IOM y – OUT D04..D07
DM IOM x – IN D10/D11 ... command IOM z – OUT D00..D03
DM IOM x – IN D14/D15 ... command IOM z – OUT D04..D07
Engineering via SICAM WEB
219