Diagnosis Of The Time; Diagnosis Of The Open-/Closed-Loop Control Function - Siemens SICAM CMIC User Manual

Remote terminal units
Table of Contents

Advertisement

Service
6.3.3.3

Diagnosis of the Time

Via the menu Time you get to the time diagnosis. Here the time state is displayed.
The time state indicates whether the time has a daylight saving offset and is set and valid.
Errors with the time synchronization are recorded in
·
Menu Diagnosis
·
Menu History
6.3.3.4

Diagnosis of the Open-/Closed-Loop Control Function

For the supervision of the open-/closed-loop control function several diagnosis functions are
available.
Errors due to the logic operations or by means of external influence are displayed in the menu
History . The corresponding supervision routines are performed automatically, no user set-
tings are required therefore.
Errors due to the syntax or program size are recognized automatically after the loading and
displayed in the status log (see section 5.2.2.1.1,
If the IL was loaded offline (via storage in the root directory of the SD card), you can start the
syntax check manually in the menu Logic .
·
Click on the button
The check result is displayed in the bottom tool bar. In case of error the details are displayed
in the status log.
·
Click on the global button
308
Import Application
, if you want to read the status log
SICAM RTUs, User Manual SICAM CMIC
Program).
DC8-001-2.09, Edition 08.2016