Engineering via SICAM WEB
5.1.10.2.1 Supported Type Identifications and Possible Values
Type Identification
Single-point information
(TI 30)
Double-point information
(TI 31)
Single command (TI 45)
Double command (TI 46)
Tap position command (TI 47)
Counter value (TI 37)
Measured value normalized
(TI 34)
Measured value scaled (TI 35)
Measured value short floating
point (TI 36)
Setpoint normalized (TI 48)
Setpoint scaled (TI 49)
Setpoint short floating point
(TI 50)
The values are converted depending on the type identification (TI). Analog values are dis-
played as conditioned values.
The data format of the displayed inputs corresponds to the setting of the respective data point
on the I/O module (signal list).
228
Possible value
Off (0)
On (1)
Intermediate (00),
Off (01)
On (10)
Error (11)
Off (0)
On (1)
Terminated (00)
Off (01)
On (10)
Error (11)
Terminated (00)
Lower (01)
Higher (10)
Error (11)
-1...+1
-32768...+32767 (15 Bit + sign)
15
15
-1.000•10
...+1.000•10
-1...+1
-32768...+32767 (15 Bit + sign)
15
15
-1.000•10
...+1.000•10
Value from device without conversion
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016