Siemens SICAM CMIC User Manual page 206

Remote terminal units
Table of Contents

Advertisement

Engineering via SICAM WEB
Processing type
SW_COSPHI - software
power factor
SW_CT_FDIR_I>_I>>
SW_CT_FDIR_IN
SW_CT_MV_SELECTIO
N
SW_CT_PDIR
SW_F – software fre-
quency
206
Parameter
OV_suppr_t
standard load
thresh_additive
thresh_uncond
I>
I>>
I>>_t
I>_t
t_reset
IN>
IN>_Idir
IN>_ground_type
IN>_U0
IN>_U0_t
IN>_t
t_reset
measured_value_selection
thresh_additive
thresh_uncond
thresh_additive
Meaning
OV suppression time in seconds, 0=no OV
suppression
0 to 255
The measuring range can be adapted with
changing the load (S)
NO/YES
Change threshold in % of X_100% (S) AI_T:
% of temperature range
0 to 1000.0
Change threshold in % of X_100% (S) AI_T:
% of temperature range
0 to 103.00
Trip value in ampere for overcurrent detection
for short circuit 0: function disabled
50 to 2000
Trip value in ampere for overcurrent detection
for short circuit 0: function disabled
50 to 2000
Time delay for overcurrent detection
0.04 to 60
Time delay for overcurrent detection
0.04 to 60
Auto reset time
0 = function disabled
Trip value in ampere for ground fault 0: func-
tion disabled
0.4 to 2000
Earth current for earth fault detection using
the wattmetric method 0: function disabled
0.2 to 30
Ground point treatment method
· solid
· isolated
· resonant
Ground point displacement voltage in procent
of primary voltage 0: function disabled
0 to 100
Ground point displacement voltage time delay
0.04 to 60
Time delay for ground fault indication
0.04 to 60
Auto reset time
0 = function disabled
Selection of a measured value
Change threshold in % of X_100% (S) AI_T:
% of temperature range
0 to 1000.0
Change threshold in % of X_100% (S) AI_T:
% of temperature range
0 to 103.00
Change threshold in % of X_100% (S) AI_T:
% of temperature range
0 to 1000.0
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016