Example: SICAM CMIC + 6 ext. SICAM I/O modules
Thermical space ..................................................... 30
SICAM CMIC housing ............................................128
SICAM CMIC coupling module .............................. 12,5
SICAM I/O modules (6 x 30) ..................................180
(30 mm for each module; max. 6 permitted)
End clamp ................................................................ 5
Horizontal space requirement (mm)..................... 355,5
30
128
F1
F2
1.3.3

Cable Duct

Cable ducts are recommended for the cabling above and below the device. The minimum dis-
tance from the device to the cable duct is 30 mm.
Note
When using a cable duct with 100 mm depth below the device, it is necessary to keep a 50 mm minimum
distance between device and cable duct to operate the locking hook.
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016