Alter Status provides a programming level for changing operating parameters such as detector
sensitivity, Walk Test, changing system time/date and disabling/enabling points. Alter Status is
accessible with the Master Password and with User Passwords programmed for Alter Status.
Soft Keys
All soft key selections (except BACK) are menu selections. Press to display the desired menu.

4.1 Disable/Enable Point Selection

.
Soft Keys
POINT: Press this soft key to identify the type of point to disable/enable: the choices that will
appear in parentheses next to the point format are DETECTOR, MODULE, LOGIC ZONE,
GENERAL ZONE, or DAA SPEAKER CIRCUIT. Enter the address of the point using the keyboard.
If there is an event in the display area, that address will be the default. If no event is present, the
default format will be that of a detector.
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012

Section 4: Alter Status

L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
T U E J A N 2 5 , 2 0 1 1
A L T E R S T A T U S
D I S A B L E / E N A B L E
D E T E C T O R S E N S I T I V I T Y
C L E A R V E R I F Y C O U N T S
C L E A R H I S T O R Y
Figure 4.1 Alter Status Screen
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
T U E J A N 2 5 , 2 0 1 1
P O I N T S E L E C T
P O I N T S E L E C T :
N 1 0 4 L y y D z z z D E T E C T O R )
N E X T S E L E C T I O N
P R E V I O U S S E L E C T I O N
Figure 4.2 Point Select for Disable/Enable Screen
W A L K T E S T
C H A N G E T I M E / D A T E
C O N T R O L O N / O F F
B A C K
A C C E P T
B A C K
71