B.2: Nfpa Releasing Applications; B.3: Abort Switches - Honeywell nfs2-3030 Programming Manual

Fire alarm control panel
Hide thumbs Also See for nfs2-3030:
Table of Contents

Advertisement

NFPA Releasing Applications
B.2 NFPA Releasing Applications
This control panel can be used for agent release or preaction/deluge control applications. In a
properly configured system with compatible, listed actuating and initiating devices, this control
panel complies with the following NFPA standards for installation in accordance with the
acceptable standard:
B.3 Abort Switches
The control panel provides for four types of abort switches - ULI, IRI, NYC, and AHJ - each of
which will affect the operation of the delay timer in the releasing zone. For example, an NYC Abort
Switch for releasing zone ZR05 affects only the delay timer in ZR05.
When an initiating device activates, pressing and holding the abort switch will prevent the control
panel from sending the command to dump releasing agents when the Delay Time expires.
Requirements for using an abort switch include the following:
• A monitor module must be connected to a UL-listed abort station, such as the NBG-12LRA
shown below.
• The monitor module must be programmed with the Type Code
• An abort switch shall not be used with a preaction system.
This section contains information on each type of abort switch.
Example of an Abort Switch Application
The figure below contains an illustration for an abort switch application configuration using
releasing zone ZR05 as an example. The configuration includes:
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Standard
NFPA 13
Sprinkler Systems
NFPA 15
Water Spray Systems
NFPA 16
Foam-water Deluge and Foam-water Spray Systems
NFPA 17
Dry Chemical Extinguishing Systems
NFPA 17A
Wet Chemical Extinguishing Systems
NFPA 2001
Clean Agent Fire Extinguishing Systems
Table B.1 NFPA Standards for Releasing Applications
Abort Switch
Manual Agent
Release lever
Figure B.1 UL-listed Abort Station
Covers
SYSTEM
SYSTEM
NORMAL
ACTIVATED
NBG-12LRA station with Abort Switch
Releasing Applications
.
ABORT SWITCH
97