Honeywell nfs2-3030 Programming Manual page 56

Fire alarm control panel
Hide thumbs Also See for nfs2-3030:
Table of Contents

Advertisement

Program
Soft Keys
LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (ON) will continue to function across all the panel's SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with "fire" point types will activate SLC outputs with "fire"
point types. Refer to Appendix G.3, "Type Codes for Input Devices", on page 138 for Type Code
point types. Default: OFF
NOTE: The panel setting
device level.
ZONE MAP: Displays the zones mapped to this point. The default value assigned to control modules
during initial programming is Z000 at Position 1 (refer to Figure 3.45), with the exception of control modules
with the following Type IDs: TELEPHONE, GEN ALARM, GEN SUPERVIS, GEN TROUBLE, and
TROUBLE PEND.
To add or delete zones, press this soft key to proceed to the Module Zone Map screen. Refer to
"Zone Map" on page 45 for an illustration and explanation of the Detector Zone Map screen. The
Module Zone Map screen is the same except that Module replaces Detector in the title and the
module address appears instead of the detector address. Up to ten general, logic, release, special or
trouble zones may be mapped to a control module. Position 1 has additional functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
Note that the group zone disable command has no effect on general alarm zone Z000.
WALK TEST: This field determines if the output will activate during Walk Test. Values are ON
(the output will activate) and OFF (the output will not activate). Default: OFF.
NOTE:
will not appear when the screen displays: REL END BELL, RELEASE CKT, REL CKT ULC, REL.
FORM C, REL AUDIBLE, INST RELEASE, NONRESET CTL, TELEPHONE, and FORM-C RESET.
The FMM-1 module with SMOKE CONV, HEAT DETECT, or SMOKE DETECT does not participate
in Walk Test.
SWITCH INHIBIT: This field determines whether a user can manually activate an output.
Values are YES (can not be activated manually) or NO (can be activated manually). Default: NO
SILENCEABLE: This field determines whether the user can manually silence an activated output.
Values are as follows:
NO
YES - RESOUND FIRE
YES - RESOUND SUPERV
YES - RESOUND SECURITY
YES - RESOUND TROUBLE
YES - NO RESOUND
NOTE: This soft key will not appear for modules with Type ID codes where silence is not optional.
56
LCM LOCAL MODE
The following Type ID codes do not participate in Walk Test, and the WALK TEST soft key
Not manually silenceable
Silenceable, resound on fire alarm events
Silenceable, resound on supervisory events Network and Local Resound
Silenceable, resound on security events
Silenceable, resound for trouble
Silenceable, does not resound
must be set to Yes for local mode to work at the
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Point Program
Network and Local Resound
Network and Local Resound
Local Resound