Alter Status
Soft Keys
POINT: Press this soft key to enter the point address or general zone number (except Z000) to be
forced on or off.
NOTE: A module with a releasing Type ID can not be forced.
NEXT/PREVIOUS SELECTION: Press to progress to the next or previous point on the loop, or
the next or previous general zone.
ACCEPT: Press to continue to the Control On or Control Off screen.
4.8.1 Control Off
One of the following two screens will display when a point or general zone is selected and accepted
in the previous screen.
If the selected point or zone is active, the Control Off screen will appear.
Soft Keys
FORCE OFF: Press this soft key to change the state of the control module or general zone from
A U T O M A T I C A C T I V E
NOTE: A module with a releasing Type ID cannot be forced.
84
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
T U E J A N 2 5 , 2 0 1 1
C O N T R O L O N / O F F :
A U T O M A T I C
A C T I V E
E L E V A T O R R E C A L L
F I F T H F L O O R
F O R C E O F F
Figure 4.17 Control Off Screen
to
A U T O M A T I C I N A C T I V E .
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Control On/Off Point Select
N 1 1 4 L 0 3 M 0 5 2
E A S T W I N G
Z 0 0 0
C O N T R O L