Walk Test
4.6.4 Devices Test Selection
This field will appear only for a beam detector with an integral sensitivity test feature.
Soft Keys
START TROUBLE TEST:Press this key to generate a Trouble on the selected detector.
START ALARM TEST: Press to generate an Alarm on the selected detector.
START OBSCURATION TEST: Press to perform an Obscuration Test on the selected Beam
detector. (Beam detectors only.)
START PREALARM TEST: Press to perform a Prealarm Test on the selected device.
ABORT: Press to stop the Walk Test.
NOTE: The Trouble, Alarm and Obscuration tests described above are additional tools provided to
ascertain the functionality of a detector. They are not a substitute for periodic maintenance and
sensitivity verification per NFPA 72.
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
T R O U B L E
P R O G M O D E A C T I V A T E D
L A K E V I E W G E N E R A L H O S P I T A L
1 0 : 2 2 : 3 4 A
T U E J A N 2 5 , 2 0 1 1
W A L K T E S T I N P R O G R E S S
S E T T I N G S : B A S I C , A U D I B L E , P A N E L
S T A R T T R O U B L E T E S T
S T A R T A L A R M T E S T
S T A R T O B S C U R A T I O N T E S T
Figure 4.12 Devices Test Selection Screen
S T A R T P R E A L A R M T E S T
A B O R T