Abort Switches
How to Program a Release Form-C Circuit
NOTE: An output with a
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable; No
Walk Test.
The following contains information needed to program a Release Form-C circuit for an SLC
Form-C relay output module
Description An SLC output module, configured as a relay, programmed to activate an output by
opening or closing a switch. Typical applications include closing doors and air handlers.
Program Select an SLC output module to use as a Releasing Form-C Circuit. While
programming the point (refer to the Point Programming section of this manual for instructions),
1.
Select the
2.
Enter the number of the desired Releasing Zone into the module's zone map. The releasing
zone must be fully programmed (refer to Section 3.4.4, "Releasing Zone", on page 57).
Example A programming example of a control module programmed as a Release Form-C circuit
for Releasing Zone ZR05.
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
.
REL
FORM C
.
.
Type Code,
REL
FORM C
Monitor
Detector
Module
SLC
output
output
module
module
Type Code
Type Code
.
REL
FORM C
RELEASE CKT
For example, an output module, configured as a Form-C relay,
activates simultaneously with other outputs (modules A, B & C)
Figure B.16 Control Module Configured as a Release Form-C Circuit
Type Code requires the following selections: a Releasing
Detector
ZR05
SLC
SLC
output
module
A
B
Type Code
RELEASE CKT
programmed for ZR05.
Releasing Applications
Detector
Output
module
C
Type Code
REL AUDIBLE
113