Type Codes
REL. FORM C†
,
‡
N
RELEASE
N
CKT†
,
‡
REL CKT ULC†
,
‡
N
REL END BELL
N
REL AUDIBLE
Y
FORM C RESET†
N
*
Values represent program defaults
†
With LCM-320 revision 2.0 and higher, this Type Code has external power supervision (FlashScan only). An external power-supervision relay is not required. Note
that Type Codes RELAY, REL FORM C, and FORM C RESET are for use only with FRM-1 modules. Refer to the section on devices requiring external power
supervision in this panel's installation manual
‡
The FCM-1-REL checks for shorts with all releasing type codes.
G.5 FlashScan Codes
This section provides a list of FlashScan Codes for FlashScan SLC devices. Select from these codes
to define the type of point:
142
Y
N
Form-C relay
(SLC only)
Y
N
NAC (SLC only)
Y
N
NAC (SLC only)
Y
N
NAC
Y
N
NAC
Y
N
Form-C Relay
(SLC only)
Table G.3 SLC Control Module Type Codes (2 of 2)
Label
Device/Point
4-20MA
FMM-4-20
ACCLIMATE
FAPT-751, FAPT-851
BEAM
FSB-200,FSB-200S
IQUAD
FSC-851
CONTROL
FCM-1
HEAT
FST-751/R, FST-851/R
HIGH HEAT
FST-851H
ION
FSI-751, FSI-851
LASER
FSL-751
MANUAL STATION
FSM-101 (NBG-12LX Series)
MINI/DUAL MONITOR
FMM-101,FDM-1
MONITOR
FMM-1
PHOTO
FSP-751,FSD-751P/RP, FSP-851, FSD-751PL/RPL, FSH-751
PHOTO/HEAT
FSP-751T, FSP-851T
PHOTO/CO
FCO-851
PS MON
PS MON
PS CONTROL
ACPS CONTROL
PS RELAY
ACPS RELAY
RELAY
FRM-1
RELEASE
FCM-1-REL
RFX MON
RFX MON
RFX SMOKE
SDRF-751
RFX SUP
RFX SUP
TELEPHONE
FTM-1
XPIQ BATTERY
XPIQ BAT MON
XPIQ GND FLT
XPIQ EF MON
XPIQ AC
XPIQ AC MON
XPIQ TROUBLE
XPIQ GEN MON
XPIQ STROBE
XPIQ STROBE
XPIQ SPEAKER
XPIQ SPEAKER
XPIQ TELEPHONE
XPIQ TELEPHONE
Table G.4 FlashScan Codes (1 of 2)
n/a
Directs relay outputs to perform a releasing function.
n/a
Directs outputs to perform a releasing
function.Supervised for open circuits and ground
faults. Short = normal
n/a
Directs outputs to perform a release function as
required by ULC.
n/a
Activates NAC audio or visual device when
releasing circuits shut off.
n/a
Activates audio or visual devices steady when
releasing starts.
n/a
Relay module used to interrupt 24V power to four-
wire conventional detectors for 30 seconds upon
reset. Used in conjunction with a monitor module
with a conventional detector Type ID
FlashScan Codes
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
FlashScan Codes