Releasing Applications
How to Program a Release Circuit
NOTE: A Release Circuit with this Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable; No
Walk Test.
NOTE: Do not use a Release Circuit for the following: An application requiring ULC Listing; An
application requiring power-limited energy cable.
The following contains information needed to program a Release Circuit for an SLC output circuit
.
module
Description An SLC output module used to activate a releasing solenoid or other releasing
device. Multiple outputs with the
Zone. When the Releasing Zone activates, all outputs associated with the releasing zone and with
the
RELEASE CKT
An initiating device programmed to the same Releasing Zone activates (two devices if using
the Cross Zone option)
The Delay Timer for the releasing zone (if used) expires
The Abort Switch for the releasing zone (if used) is not active
Program Select an SLC output module to use as a Release Circuit. While programming the point
(refer to the Point Programming section of this manual for instructions),
1.
Select the
2.
Enter the number of the desired Releasing Zone into the module's zone map. The releasing
zone must be fully programmed (refer to Section 3.4.4, "Releasing Zone", on page 57).
Example A programming example of a control module programmed as a Release Circuit for
Releasing Zone ZR05.
112
RELEASE CKT
Type Code also activate at the same time. A Release Circuit activates when:
Type Code
RELEASE CKT
Monitor
Detector
Module
Type Code
RELEASE CKT
SLC
SLC
output
output
module
module
A
For example, all modules programmed with the RELEASE CKT
Type Code activate when the delay timer expires for ZR05. Other
outputs (modules A & B) will activate according to their
Figure B.15 Output Module Configured as a Release Circuit
Type Code can be mapped to the same Releasing
Detector
ZR05
SLC
output
module
B
programming.
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Abort Switches
Detector
Type Code
RELEASE CKT
SLC
output
module