Abort Switches
How to Program an Instant Release Circuit
NOTE: An output with an
selection (a releasing zone may be used, but is not required); an output circuit mapped to the
same zone; Switch Inhibit; Non-Silenceable; No Walk Test.
The following contains information needed to program an Instant Release circuit for an SLC output
.
module
Description An SLC output circuit module programmed to activate non-releasing devices, such
as door openers or warning sounders, without counting down delay timers. A device programmed
with the
Program Select an SLC output module to use with a releasing circuit. While programming the
point (refer to the Point Programming section of this manual for instructions),
1.
Select the
2.
Enter the number of the desired Releasing Zone into the module's zone map. The releasing
zone must be fully programmed (refer to Section 3.4.4, "Releasing Zone", on page 57).
Example A programming example of a control module programmed as an Instant Release circuit
for Releasing Zone ZR05.
How to Program a Release Code Bell Circuit
When coded output is desired to indicate different phases of a releasing operation, the panel can be
programmed using Control-By-Event (CBE) to turn on outputs set to provide the chosen codes.
Example Description In the following example, programming is shown that will
1.
Turn on an output when the first alarm activates in a releasing zone, but Cross Zone conditions
are not met. Turn it off when the Delay Timer starts.
2.
Turn on a different output when Cross Zone conditions are met and the Delay Timer activates,
and turn it off when releasing starts.
3.
Turn on a different output when releasing starts, and turn it off when the soak timer expires or
the system is reset.
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
INST RELEASE
Type Code device is supervised for open circuits and ground faults.
INST RELEASE
Type Code,
INST RELEASE
Monitor
Detector
Module
Type Code
INST RELEASE
SLC
output
output
module
module
For example, a module programmed with the
Type Code activates simultaneously with other outputs
(modules A & B) programmed for ZR05.
Figure B.18 Output Module Configured as an Instant Release Circuit
Type Code requires the following selections: a zone
Detector
ZR05
SLC
SLC
output
module
A
B
Releasing Applications
Detector
Type Code
INST RELEASE
SLC
output
module
INST RELEASE
115