Releasing Applications
How to Program an Abort Switch
The following contains information needed to program an Abort Switch for a monitor module.
Description A monitor module, connected to a UL-listed abort station (such as the Notifier
NBG-12LRA), used to monitor an abort switch for a releasing zone. Multiple monitor modules can
be programmed with the
abort switches on a conventional zone.
Program Select a monitor module for use as an Abort Switch. While programming this module
(refer to Section 3.4.2, "Module Point", on page 51 for instructions),
1.
Select the
2.
Enter the number of the desired releasing zone into the module's zone map. The releasing zone
must be fully programmed, with the Abort Switch type code included (refer to Section 3.4.4,
"Releasing Zone", on page 57).
Example A programming example of a monitor module programmed as an Abort Switch for
Releasing Zone ZR05.
106
Type Code. They will work like multiple conventional
ABORT SWITCH
Type Code.
ABORT SWITCH
SYSTEM
SYSTEM
NORMAL
ACT IVATED
Type Code
ABORT SWITCH
NBG-12LRA
station with
Abort Switch
Figure B.9 Monitor Module Configured as an Abort Switch
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Monitor
Detector
Module
R05
SLC
SLC
output
output
module
module
Abort Switches