Honeywell nfs2-3030 Programming Manual page 134

Fire alarm control panel
Hide thumbs Also See for nfs2-3030:
Table of Contents

Advertisement

CBE: Zones and Equations
Example: XZONE(Z02)
If any combination of two or more initiating devices that have been mapped to this software
zone come into alarm, then outputs mapped to this zone will activate.
The "RANGE" Operator
Each argument within the range must conform to the requirements of the governing function.
The range limit is 20 consecutive arguments.
Example: AND(RANGE(Z1,Z20))
Zone 1 through Zone 20 must all be active to activate the logic zone.
The "DIS(point argument)" Operator
Requires that the point argument be disabled for the operator to go active.
The "PRE(point argument)" Operator
Requires that the point argument be in prealarm for the operator to go active.
Example: AND(L1D1,PRE(L1D2))
The detector at address L1D1 must be active and the detector at L1D2 must be in prealarm for
this equation to go active.
The "SUP(point argument)" Operator
Requires that the point argument be in an active supervisory state for the operator to go active.
Example: OR(L1D1,SUP(L1M1))
The detector at address L1D1 must be active, or the module at L1M1 must be in an active
supervisory state, for the equation to go active.
The "FIRE(point argument)" Operator
Requires that the point argument be in an active fire alarm state for the operator to go active.
Example: AND(L1D1,FIRE(L1M1),FIRE(L1M2))
The detector at address L1D1 must be active, and the modules at L1M1 and L1M2 must be in
an active fire alarm state, for the equation to go active.
The "NON(point argument)" Operator
Requires that the point argument be in an active non-alarm state for the operator to go active.
Example: AND(L1D1,NON(L1M1))
The detector at address L1D1 must be active, and the module at address L1M1 must be in an
active non-fire alarm state, for the equation to go active.
The "SEC(point argument)" Operator
Requires that the point argument be in an active security alarm state for the operator to go
active.
Example: AND(L1M1,SEC(L1M2))
The module at address L1M1 must be active, and the module at address L1M2 must be in an
active security alarm state, for the equation to go active.
Time-based Functions
The panel supports three time-based functions: DEL, SDEL, and TIM. Special rules apply to an
equation containing a time-based function:
• Only one time-based function may be used in an equation.
• The time-based function must appear only once, as the first entry of the equation.
• It may not be nested within parentheses in the equation.
• Logic functions may be used in an equation that begins with a DEL or SDEL time-based
function: however, they must appear within parentheses following the time-based function.
Delay and duration times are in 24-hour format (HHMMSS); the allowable range is 00:00:00 to
23:59:59.
The "DEL" Function
134
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Equations

Advertisement

Table of Contents
loading

Table of Contents