PREALARM: Press this softkey to select ALERT or ACTION for the Prealarm function. Refer to
the section on Prealarm in Appendix D, "Intelligent Sensing Applications" for a description of
Alert and Action.
SILENCEABLE: This field determines whether the user can manually silence a detector's
activated sounder/relay base. Values are as follows:
NO
YES - RESOUND FIRE
YES - RESOUND SUPERV
YES - NO RESOUND
NOTE: In network applications, specific nodes can be excluded from having the ability to initiate a
resound on the local fire alarm panel. This is programmable via VeriFire Tools. Refer to the VeriFire Tools
help file.
INTELLIGENT SOUNDER: Press this softkey to select YES if an Intelligent Sounder Base is
installed for this detector.
SOUNDER BASE SETUP: Press this softkey to proceed to the Sounder Base Setup screen. This
option will only be available if the INTELLIGENT SOUNDER is set to YES.
CO PRE-ALARM: Press this softkey to select YES or NO to enable the CO Prealarm function for
the PHOTO/CO smoke detector. This field is only available when programming the PHOTO/CO
smoke detector.
Sounder Base Setup
Soft Keys
A U X T O N E 1 :
C U S T O M
A U X T O N E 1 C O N T R O L :
will control the activation of the first auxiliary tone of the intelligent sounder base.
A U X T O N E 2 :
C U S T O M
A U X T O N E 2 C O N T R O L :
will control the activation of the second auxiliary tone of the intelligent sounder base.
50
Not manually silenceable
Silenceable, resound on fire alarm events
Silenceable, resound on supervisory events Network and Local Resound
Silenceable, does not resound
S O U N D E R B A S E S E T U P
A U X T O N E 1 : T E M P - 3
A U X T O N E 1 C O N T R O L : Z L 0 0 4 0
A U X T O N E 2 : T E M P - 4
A U X T O N E 2 C O N T R O L : Z L O O 4 1
V O L U M E : H I G H
Figure 3.39 Sounder Base Setup Screen
Press this softkey to select
for the first auxiliary tone of the intelligent sounder base.
Press this softkey to enter the Logic, General or Trouble Zone that
Press this softkey to select
for the second auxiliary tone of the intelligent sounder base.
Press this softkey to enter the Logic, General or Trouble Zone that
L 0 3 D 1 2 3
,
C O N T I N U O U S
T E M P - 3
,
C O N T I N U O U S
T E M P - 3
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Point Program
Network and Local Resound
A C C E P T
B A C K
,
,
or
T E M P - 4
M A R C H
,
,
or
T E M P - 4
M A R C H