Releasing Applications
How to Program a Release Audible Circuit
NOTE: An output with a
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit.
The following contains information needed to program a Release Audible circuit for an SLC output
.
module
Description An output module programmed to activate an audio or visual device when all
releasing outputs, programmed to the same Releasing Zone, turn on. Multiple outputs with the
REL AUDIBLE
activates, all outputs with the
Program Select a control module to use as a releasing circuit. While programming the point
(refer to the Point Programming section of this manual for instructions),
1.
Select the
2.
Enter the number of the desired Releasing Zone into the module's zone map. The releasing
zone must be fully programmed (refer to Section 3.4.4, "Releasing Zone", on page 57).
Example A programming example of a control module programmed as a Release Audible circuit
for Releasing ZoneZR05.
114
REL AUDIBLE
Type Code can be mapped to the same Releasing Zone. When the Releasing Zone
REL AUDIBLE
Type Code,
REL AUDIBLE
Monitor
Detector
Module
SLC
Output
output
module
module
Type Code
Type Code
RELEASE CKT
REL AUDIBLE
For example, an output module programmed with the
Type Code activates simultaneously with other
AUDIBLE
outputs (modules A & B) programmed for ZR05.
Figure B.17 Output Module Configured as a Release Audible Circuit
Type Code requires the following selections: a Releasing
Type Code activate at the same time.
Detector
ZR05
SLC
output
module
A
B
Type Code
RELEASE CKT
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Abort Switches
Detector
Output
module
Type Code
REL AUDIBLE
REL