Point Program
LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (ON) will continue to function across all the panel's SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with "fire" point types will activate SLC outputs with "fire"
point types. Refer to Appendix G.3, "Type Codes for Input Devices", on page 138 for Type Code
point types. This setting is fixed at OFF for the FMM-4-20 module. Default: OFF
NOTE: The panel setting LCM LOCAL MODE must be set to YES for local mode to work at the
device level.
4-20 DEVICE SETUP: Press to go to FMM-4-20 programming. (Refer to "FMM-4-20 Monitor
Module Programming" on page 53"FMM-4-20 Monitor Module Programming" on page 53) This
field appears only when FMM-420 appears as the module's Type Code label.
MORE: Press to access the third Module Point Programming Screen.
ACCEPT: Press to save entries made on this screen and to return to the previous screen.
FMM-4-20 Monitor Module Programming
Pressing the 4-20 DEVICE SETUP soft key at the Module Point Programming screen will display
this screen.
Soft Keys
4 M A S C A L E V A L U E :
2 0 M A S C A L E V A L U E :
U N I T S :
H Y S T E R E S I S :
Default: 0
T H R E S H O L D S E T U P :
on page 54)
A C C E P T :
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
M O D U L E P O I N T P R O G R A M M I N G
4 M A S C A L E V A L U E : 0 . 0 0
2 0 M A S C A L E V A L U E : 2 0 0 0 . 0 0
U N I T S : P P M
H Y S T E R E S I S : 0 2 . 0 %
T H R E S H O L D S E T U P
Figure 3.42 FMM-4-20 Device Setup Screen
Enter the 4 mA value.
Enter the 20 mA value.
Type in the kind of units. (5 spaces.)
Enter the hysteresis value in decimals as a percentage of the overall 4 to 20 mA range.
Press to continue to the
Press to save entries made on this screen.
L 0 3 M 1 5 0
A C C E P T
T H R E S H O L D S E T U P
Program
B A C K
screen. (Refer to Figure 3.43