Releasing Applications
How to Program a Release End Bell Circuit
NOTE: A releasing circuit with this Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable;
No Walk Test.
The following contains information needed to program a Release End Bell circuit for an SLC
output module
Description An SLC output module to activate an audible or visual device when releasing
devices shut off when soak time is complete. Multiple outputs with the
can be mapped to the same Releasing Zone. When the soak timer has expired, all outputs with the
REL END BELL
system is reset.
Program Select an SLC output module to use as a Release End Bell circuit. While programming
the point (refer to the Point Programming section of this manual for instructions),
1.
Select the
2.
Enter the number of the desired releasing zone into the module's zone map. The releasing zone
must be fully programmed (refer to Section 3.4.2, "Module Point", on page 51).
Example A programming example of a control module programmed as a Release End Bell for
Releasing Zone ZR05.
110
.
Type Code activate at the same time. A
Type Code,
REL END BELL
Monitor
Detector
Module
Output
output
module
module
Type Code
Type Code
RELEASE CKT
REL END BELL
For example, a module programmed with the
Type Code activates when the ZR05 soak timer expires.
Figure B.13 Output Module Configured as a Release End Bell Circuit
REL END BELL
Detector
ZR05
SLC
SLC
output
module
Type Code
RELEASE CKT
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Abort Switches
Type Code
REL END BELL
circuit remains on until the
Detector
Output
module
Type Code
REL AUDIBLE
REL END BELL