5: Panel Timers (Menu 1) - Honeywell nfs2-3030 Programming Manual

Fire alarm control panel
Hide thumbs Also See for nfs2-3030:
Table of Contents

Advertisement

Program
S I L E N C E A B L E W A T E R F L O W :
incoming Waterflow events will not be allowed to be silenced. If set to
events can be silenced.
Default:
Reminder Menu
Press the Reminder Menu soft key on the Panel Program Menu 1 screen to set the trouble reminder.
Soft Keys
TROUBLE REMINDER: Press this soft key to toggle between the two possibilities:
YES: Choose this to initiate a daily 11:00AM reminder that there are uncleared troubles in the
system. The reminder will appear on the screen and will sound a piezo (if the piezo is enabled).
NO: Choose this if no reminder is desired. Default: YES
ACCEPT: Press this soft key to save the information entered on this screen.
3.2.5 Panel Timers (Menu 1)
Press the Panel Timers soft key on the Panel Program Menu 1 screen to display the following
screen.
26
N O
T R O U B L E R E M I N D E R : Y E S
Figure 3.13 Reminder Menu Screen
V E R I F Y T I M E : 3 0
M A X I M U M V E R I F I C A T I O N C O U N T : 0 0
A C F A I L D E L A Y :
S I L E N C E I N H I B I T : 0 0 : 0 0
A U T O S I L E N C E : O F F
Figure 3.14 Panel Timers (Menu 1) Screen
If the
S I L E N C E A B L E W A T E R F L O W
R E M I N D E R M E N U
P A N E L T I M E R S
V E R I F Y = P R E A L A R M :
2
H O U R S
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Panel Program
option is set to
,
N O
, incoming Waterflow
Y E S
A C C E P T
B A C K
N O
M O R E
A C C E P T
B A C K