Panel Program
ACS Point
Mode
... will act like the System Reset button on the panel,
RESET
resetting the panel when its button is pushed.
... will act like the Drill button on the panel, initiating a fire
DRILL
drill when its button is pushed.
...will cause the associated input to become an active
ENABLE
audio source on Noti•Fire•Net. The user may then
PAGING FROM
___
choose to activate specific PAM points on remote Digital
Voice Commands to use this network input, or to perform
a paging function such as ALL CALL from this input.
ALL CALL
This point will activate ALL CALL. (Speaker Circuits will
turn on according to programming) to a DVC only.
Mapping must be to a DVC node. 
If an AMG is connected to this panel, ALL CALL can be
activated ONLY by the ALL CALL switch on the AMG. Do
not program any other annunciators for ALL CALL.
PAGE
...will, when pressed after a Page Enable, allow PAGE
INACTIVE paging from that source. The Special Paging
INACTIVE
Function map programming at the DVC will receive the
page function.
...will, when pressed after a Page Enable, allow Page
PAGE EVAC
Evac paging from that source. The Special Paging
Function map programming at the DVC will receive the
page function.
...will, when pressed after a Page Enable, allow Page
PAGE ALERT
Alert paging from that source. The Special Paging
Function map programming at the DVC will receive the
page function.
FFT-NFN
....will, when pressed:
• Notify a DVC in the map format
Nxxx,Nxxx,NxxxLyyMzzz or Nxxx,Nxxx,NxxxAyyT to
open the FFT-NFN link and turn on the mapped FFT
point or riser. A second press will notify the DVC to
turn off that FFT point or riser and determine whether
the FFT-NFN link should be closed or remain open.
• Notify a DVC in the map format Nxxx,Nxxx to close
or open the FFT-NFN link between two DVCs.
... will show the current state of the CO element for the
CO MONITOR
specified point entered.
Table 3.5 ACS Point Mapping: Explanation of Point Modes (2 of 2)
CAUTION:
!
WHEN A DISABLED OUTPUT IS ENABLED, IT WILL BE AFFECTED BY CONDITIONS EXISTING
IN THE SYSTEM THAT WOULD NORMALLY AFFECT IT. FOR EXAMPLE, WHEN A CONDITION
EXISTS IN THE SYSTEM THAT WOULD NORMALLY TURN THE OUTPUT ON, THE OUTPUT
WILL TURN ON WHEN IT IS ENABLED.
SOURCE: Pressing this soft key will select the SOURCE field and also toggle between display
formats if a point value is allowed. Enter a point or zone, or the panel's node number if the mode
type is a system function such as acknowledge or reset.
Up to eight sources are allowed when CONTROL mode is chosen.
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Function:
The point...
Explanation
No LED will ever light at this point.
The Point Active LED lights when the button is pushed
and the system has entered the drill state. The Status
(trouble) LED will never light.
The Point Active LED is lit if a corresponding mapped
point is active. The Status (trouble) LED is on when a
point or zone is in trouble.
The Point Active LED is lit if a corresponding mapped
point is active. The Status (trouble) LED is on when a
point or zone is in trouble.
The Point Active LED is lit if a corresponding mapped
point is active. The Status (trouble) LED is on when a
point or zone is in trouble.
The Point Active LED is lit if a corresponding mapped
point is active. The Status (trouble) LED is on when a
point or zone is in trouble.
The Point Active LED is lit if a corresponding mapped
point is active. The Status (trouble) LED is on when a
point or zone is in trouble.
The Point Active LED is lit if a corresponding mapped
point is active. The Status (trouble) LED is on when a
point or zone is in trouble.
The Point Active LED is lit if a corresponding mapped
point is active. The Status (trouble) LED is on when a
point is in trouble. This point is specifically used to
annunciate the CO element of the PHOTO/CO detector.
Program