Program
3.2.6 Panel Timers (Menu 2)
Press the MORE soft key on the Panel Timers Menu 1 screen to display the following screen.
Soft Keys
PAS: Press to toggle between the choices of OFF or ON for PAS (Positive Alarm Sequence). Refer
to Appendix C, "Special Zone Outputs" for an explanation of this option. Default: OFF
PRESIGNAL DELAY: Press to enter a value of 00:00 (OFF) or a value of 1:00 to 3:00 minutes
(in the format MM:SS, where MM= minutes, SS=seconds). This feature initially causes alarm
signals to sound only in specific areas, monitored by qualified personnel. This allows delay of the
alarm for up to 3 minutes after the start of alarm processing. Refer to Appendix C, "Special Zone
Outputs" for further explanation of this option. Default: 3:00
DEFAULT TIMERS: Press this soft key to activate default settings for the following:
ACCEPT: Press this soft key to save the information entered on this screen and return to the
previous screen.
3.2.7 LCD Programming
The LCD Programming screen allows the user to vary the contrast of the display and turn the
backlight on or off.
28
P A N E L T I M E R S
P A S : O F F
P R E S I G N A L D E L A Y : M M : S S
D E F A U L T T I M E R S
Figure 3.15 Panel Timers (Menu 2) Screen
Program setting for:
Verify Time
Max. Verify
AC Fail Delay
Silence Inhibit
Auto Silence
Verify=Prealarm
PAS
Presignal Delay
Table 3.4 Default Timers
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
A C C E P T
B A C K
Default:
30 seconds
20
8 hours
0 (disabled)
Off
No
OFF
3 minutes
Panel Program