Configure Ethernet Connection - GE D60 Instruction Manual

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

ADD DEVICE TO SOFTWARE
3
10. Enter the COM port used by the computer, the baud rate, and parity settings from the front panel
SETUP  COMMUNICATIONS  SERIAL PORTS
 PRODUCT SETUP  COMMUNICATIONS  MODBUS PROTOCOL  MODBUS SLAVE ADDRESS
fields.
Baud Rate — Typically 19200 for RS232 and higher for RS485. Both modems need to use the same rate.
Parity — Set to None if unsure
Bits — Set to 8 if unsure
Stop Bits — Set to 1 if unsure
Post Terminal Window — Enable this option if you have a SEL-203x Communications Processor, such as an SEL-2030
or SEL-2032. This option enables display of a terminal window to allow interaction with the other device.
11. Click the Read Order Code button to connect to the D60 and upload the order code to the software. If a
communications error occurs, ensure that the EnerVista software serial communications values entered in the
previous step correspond to the relay setting values, and also ensure that the same IP address is not assigned to
multiple D60 ports.
12. Click the OK button when the relay order code has been received. The new device is added to the Online Window.
The device has been configured for serial communications. Proceed to the Connect to the D60 section to begin
communication.

3.7.3 Configure Ethernet connection

You connect the Ethernet cable, define a site, then add the relay as a device at that site. The computer and UR device must
be on the same subnet.
1.
Connect the Ethernet network cable to the Ethernet port on the back of the device.
3-58
Figure 3-60: Configuring serial communication
menu, and the relay slave address setting from the front panel
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
SETTINGS  PRODUCT
SETTINGS
menu in their respective