2.1 2.1 Area of application
This lifting station pumps wastewater with and without se-
wagethat occurs below the sewer and backwater level fully
automatically into the sewage system in accordance with the
requirements of DIN 1986. They are only suitable for use for
domestic wastewater, for example in single family and mul-
tifamily homes, hotels and restaurants, department stores,
hospitals, schools or similar commercial applications.
In case the area of application will not allow down time due
to the breakdown of a single pump system, the lifting station
must be equipped with a second pump of the same capaci-
ty which switches on immediately when required (twin stati-
on instead of single station).

2.2 Description of the system

The KESSEL Aqualift
®
ting current and consists of the following main parts:
1.1
1.7
1.
A gas and water tight collecting tank made of LLD-
1.1 A wastewater pump with 5 meter power cable
PE (low linear density polyethylene), with
1.2 Pneumatic level control with 5 m cable
1.3 Access / cleaning opening
1.4 Inlet connection for DN 100 drainage pipe
1.5 DN 70 ventilation connection
1.6 DN 40 connection for emergency manual diaphragm
pump
1.7 DN 100 outlet connection with integrated non-return flap
and flap release lever
1.8 Areas for connection of additional inlets
F lifting station operates on alterna-
41

2. General

The KESSEL lifting station Aqualift
for free-standing installation in frost-protected rooms. The in-
cluded control unit must be mounted in a flood-proof, dry and
frost-protected area. The system's wastewater pumps are
equipped with a single-vane impeller and have a free pas-
sage of 40 mm. The pressure pipe connection must be size
DN 80 at a minimum, the ventilation pipes must be size DN
70 at a minimum. Abrasive media must be kept away from
the pump's impeller.
The systems are suitable for constant wastewater tempera-
tures up to 35°C. A maximum temperature of 60°C is per-
missible briefly (up to 10 minutes).
1.2
1.5
1.3
1.4
1.6
1.8
(see illustrations in chapter 9)
2.
2. Electrical control unit
3.1 Brackets with screws and dowels for fixing the pump
3.
3. Accessory parts (not illustrated)
body to the floor
3.2 Rubber connection coupling stainless steel clamps for
the pressure pipe connection
3.3 Sound-insulating underlay mat Mono: Art. no. 28692
Duo: Art. no. 28693
A detailed description of the system set-up can be found in
chapter 10, Spare parts.