E7" Outdoor Unit: Malfunction Of Outdoor Unit Fan Motor - Daikin RTSQ20PY1 Service Manual

Vrv iii-c r-410a heat pump 50hz
Hide thumbs Also See for RTSQ20PY1:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
E7
4.19 "
" Outdoor Unit: Malfunction of Outdoor Unit Fan
Motor
E7
Remote
Controller
Display
Applicable
RTSQ8P~16P (Outdoor Unit)
Models
Method of
Detect a malfunction based on the current value in the inverter PCB (as for motor 2, current
value in the fan PCB).
Malfunction
Detect a malfunction for the fan motor circuit based on the number of rotation detected by hole
Detection
IC during the fan motor operation.
Malfunction
Decision
Conditions
Supposed
Causes
251
Overcurrent is detected for inverter PCB (A4P) or fan inverter PCB (A5P)
(System down is caused by 4 times of detection.)
In the condition of fan motor rotation, the number of rotation is below the fixed number for
more than 6 seconds. (System down is caused by 4 times of detection.)
Failure of fan motor
Defect or connect ion error of the connectors/ harness between the fan motor and PCB
The fan can not rotate due to any foreign substances entangled.
Clear condition: Continue normal operation for 5 minutes
SiBE31-801_C