Troubleshooting by Remote Controller
Malfunction
code
Heat
60
Reclaim
Ventilation
60
64
65
6A
6A
6F
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
215
Operation
Inspection
Unit No.
lamp
display
k
h
l
l
k
h
k
h
k
h
l
l
k
h
Malfunction contents
l
Error of external protection device (Field setting [18-
8] setting position is 02 "Overall Alarm")
l
Error of external protection device (Field setting [18-
8] setting position is 03 "Overall malfunction")
l
Indoor unit's air thermistor error
l
Outside air thermistor error
l
Damper system alarm
l
Damper system + thermistor error
l
Malfunction of simplified remote controller
SiBE31-801_C
k: ON
h: OFF
l: Blink
Page
Referred
334
334
335
335
336
337
338
Troubleshooting