Specifications
1-2 ELECTRICAL SPECIFICATIONS
Power
Name
Supply
Phase
Frequency
Voltage
Current
Minimum circuit amps
(MCA)
Maximum fuse amps
(MFA)
Full load amps (FLA)
Voltage
Minimum
range
Maximum
Notes
29
FXDQ40NBVE
Hz
50
V
A
1.0
A
15
A
0.8
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
Maximum allowable voltage range variation between phases is 2%.
FXDQ50NBVE
VE
1~
50
220-240
1.0
15
0.8
-10%
+10%
above listed range limits.
MCA/MFA : MCA = 1.25 × FLA
MFA is smaller than or equal to 4 × FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
SiBE31-801_C
FXDQ63NBVE
50
1.1
15
0.9
Specifications