SiBE31-801_C
CHECK 11
Check for overcharge of refrigerant.
In case of VRV Systems, the only way to judge as the overcharge of refrigerant is with operating
conditions due to the relationship to pressure control and electronic expansion valve control.
As information for making a judgement, refer to information provided below.
Diagnosis of overcharge of refrigerant
1. High pressure rises. Consequently, overload control is exercised to cause scant cooling
2. The superheated degree of suction gas lowers (or the wet operation is performed).
3. The subcooling degree of condensate rises. Consequently, in heating operation, the
Troubleshooting
capacity.
Consequently, the compressor becomes lower in discharge pipe temperature despite of
pressure loads.
temperature of outlet air passing through the subcooling section becomes lower.
Cooling
High pressure
Low pressure
Frequency
Heating
High pressure
Low pressure
Frequency
To maintain HP, frequency reduces
under the capacity control.
Proper quantity
Troubleshooting (Heat Reclaim Ventilation)
High-pressure
drooping control
HP gradually rises
with increase in
frequency.
(LP is maintained
at a constant level.)
To maintain LP, frequency
increases under the capacity
control.
The outdoor unit electronic expansion
valve is closed due to the overload control.
Frequency comes to
the minimum level.
(HP is maintained
at a constant level.)
LP rises due to
reduced frequency.
(Degree of overcharge)
Frequency comes to
the minimum level.
Supercooled degree
becomes higher.
(Liquid connection
pipe temperature
lowers.)
LP rises due to
reduced compressor
output.
HP drops or rises immediately
after the overload control is
complete.
LP drops due to closed
outdoor unit electronic
expansion valve.
Hot gas bypass is activated
for LP protection, i.e.,
hunting at LP.
Higher degree of overcharge