[Cancel of Emergency Operation]
To cancel the emergency operation, conduct the following setting. (Return to Factory setting.)
<RTSYQ10 to 16PY1>
k Cancel disabling the inverter compressor from operating:
Set No. 42 of setting mode 2 "Disable-inverter compressor operation" to "OFF".
k Cancel disabling the STD compressor 1 (or STD compressor 2) from operating:
Set No. 19 of setting mode 2 "Disable-STD compressor 1 or 2 operation" to "OFF".
k Cancel disabling the STD compressor 2 from operating [RTSQ14 · 16P]:
Set No. 19 of setting mode 2 "Disable-STD compressor 2 operation" to "OFF".
Test Operation
(Step)
(1) Press the MODE button (BS1) for 5
seconds or more.
(2) Press the SET button (BS2) 42 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
(Step)
(1) Press the MODE button (BS1) for 5
seconds or more.
(2) Press the SET button (BS2) 19 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) twice.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
(Step)
(1) Press the MODE button (BS1) for 5
seconds or more.
(2) Press the SET button (BS2) 19 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
k
h
l
LED display (
: ON
: OFF
H1P-----------H7P
k h h h h h h
k k h k h k h
k h h h h l h
k h h h h h l
(Factory setting)
k h h h h h h
h h k h h h h
k
h
l
LED display (
: ON
: OFF
H1P-----------H7P
k h h h h h h
k h k h h k k
k h h h h h l
k h h h h h h
(Factory setting)
k h h h h h h
h h k h h h h
k
h
l
LED display (
: ON
: OFF
H1P-----------H7P
k h h h h h h
k h k h h k k
k h h h h l h
k h h h h h h
(Factory setting)
k h h h h h h
h h k h h h h
Field Setting
: Blink)
: Blink)
: Blink)
192