E7" Malfunction Of Outdoor Unit Fan Motor - Daikin VRV II RXYQ5MY1B Service Manual

R-410a heat pump 50hz
Hide thumbs Also See for VRV II RXYQ5MY1B:
Table of Contents

Advertisement

SiE39-404

2.18 "E7" Malfunction of Outdoor Unit Fan Motor

E7
Remote
Controller
Display
Applicable
RXYQ5~48M
Models
Method of
Malfunction of fan motor system is detected according to the fan speed detected by hall IC
when the fan motor runs.
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Troubleshooting
When the fan runs with speed less than a specified one for 15 seconds or more when the fan
motor running conditions are met
When connector detecting fan speed is disconnected
When malfunction is generated 4 times, the system shuts down.
Malfunction of fan motor
The harness connector between fan motor and PC board is left in disconnected, or faulty
connector
Fan does not run due to foreign matters tangled
Clearing condition: Operate for 5 minutes (normal)
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Connector
of fan motor is
disconnected.
NO
Harness connector
between compressor
inverter PCB and fan
inverter PCB
(A2P, A3P) is
disconnected.
NO
Is there any
obstacle around
the fan?
NO
Can the fan
be turned smoothly
with hand after disconnect
the connector of
fan motor?
YES
1A
Troubleshooting by Indication on the Remote Controller
YES
YES
YES
NO
Connect the connector.
Connect the harness
connector.
Remove the obstacle.
Replace the fan motor of
outdoor unit.
(V3076)
193