Field Setting
BRC2A Type
1. Dismount the upper casing from the remote controller.
BRC2C Type
2. Press the [BS6] button (2) (field setting) to set the system to field setting mode.
3. Press the [BS2] button (3) (temperature setting "
4. Press the [BS9] button (4) (setting A) or the [BS10] button (4) (setting B) to select a Group
5. Press the [BS7] button (5) (setting/cancel) to determine the Group No. selected.
6. Press the [BS6] button (2) (field setting) to return the system to normal mode.
<CAUTION>
163
Group No. setting by simplified remote controller for centralized control.
"
") to set the Mode No. to "00".
No.
(The group numbers increase like 1-00, 1-01, · · · 1-15, 2-00, · · ·, 4-15. However, the ON/
OFF controller only displays group numbers in the range selected by the control range
setting switch.)
Even if no remote controller is used, connect a remote controller to make Group No. setting,
make setting of Group No. for central control, and then disconnect the remote controller after
the completion of setting.
To make Group No. setting, turn on the power supply of the central controller, ON/OFF
controller, and indoor unit, respectively.
MODE NO.
UNIT NO.
") or the [BS3] (3) temperature setting
(3)
(3)
(8)(2)
(7) (4)
(5) (6)
SiBE31-801_C
Group NO.
Test Operation