Daikin RTSQ20PY1 Service Manual page 29

Vrv iii-c r-410a heat pump 50hz
Hide thumbs Also See for RTSQ20PY1:
Table of Contents

Advertisement

SiBE31-801_C
1-2 ELECTRICAL SPECIFICATIONS
Power
Name
Supply
Phase
Frequency
Voltage
Current
Minimum circuit amps
(MCA)
Maximum fuse amps
(MFA)
Full load amps (FLA)
Voltage
Minimum
range
Maximum
Notes
Specifications
FXZQ20M9V1B
FXZQ25M9V1B
Hz
V
A
0.8
A
A
0.6
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
Maximum allowable voltage range variation between phases is 2%.
FXZQ32M9V1B
V1
1~
50
220-240
0.8
0.8
15
0.6
0.6
-10%
+10%
above listed range limits.
MCA/MFA : MCA = 1.25 × FLA
MFA is smaller than or equal to 4 × FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
Specifications
FXZQ40M9V1B
FXZQ50M9V1B
0.8
0.9
0.6
0.7
18