SiBE31-801_C
1-1 TECHNICAL SPECIFICATIONS
Standard Accessories
Notes
1-2 ELECTRICAL SPECIFICATIONS
Power
Name
Supply
Frequency
Voltage
Current
Minimum circuit amps
(MCA)
Maximum fuse amps
(MFA)
Full load amps (FLA)
Voltage
Minimum
range
Maximum
Notes
1-1 ELECTRICAL SPECIFICATIONS
Power
Name
Supply
Frequency
Voltage
Current
Minimum circuit amps
(MCA)
Maximum fuse amps
(MFA)
Full load amps (FLA)
Voltage
Minimum
range
Maximum
Notes
Specifications
FXFQ63P8VEB
The sound pressure values are mentioned for a unit installed with rear suction
The sound power level is an absolute value indicating the power which a sound source generates.
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
The BYCQ140CW1W has white insulations. Be informed that formation of dirt on white insulations is visibly stronger and
that it is consequently not advised to install the BYCQ140W1W decoration panel in environments exposed to
FXFQ20P8VEB
FXFQ25P8VEB
Hz
V
A
0.4
A
A
0.3
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
Maximum allowable voltage range variation between phases is 2%.
FXFQ63P8VEB
Hz
V
A
0.9
A
A
0.7
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
Maximum allowable voltage range variation between phases is 2%.
FXFQ80P8VEB
FXFQ100P8VEB
Installation and operation manual
Drain hose
Washer for hanging bracket
Screws
Sealing pads
Insulation for fitting
Clamp for drain hose
Installation guide
Drain sealing pad
equivalent refrigerant piping : 5m, level difference : 0m.
equivalent refrigerant piping : 5m, level difference : 0m.
concentrations of dirt.
FXFQ32P8VEB
VE
50
220-240
0.4
0.4
16
0.3
0.3
-10%
+10%
above listed range limits.
MCA/MFA : MCA = 1.25 × FLA
MFA is smaller than or equal to 4 × FLA
Next lower standard fuse rating minimum 16A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
FXFQ80P8VEB
FXFQ100P8VEB
VE
50
220-240
0.9
16
0.7
-10%
+10%
above listed range limits.
MCA/MFA : MCA = 1.25 × FLA
MFA is smaller than or equal to 4 × FLA
Next lower standard fuse rating minimum 16A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
Specifications
FXFQ125P8VEB
FXFQ40P8VEB
FXFQ50P8VEB
0.5
0.6
0.4
0.5
FXFQ125P8VEB
1.4
1.9
1.1
1.5
16