Daikin RTSQ20PY1 Service Manual page 184

Vrv iii-c r-410a heat pump 50hz
Hide thumbs Also See for RTSQ20PY1:
Table of Contents

Advertisement

Field Setting
173
No.
Setting item
Emergency
operation 1
(Setting for the
master unit
38
operation
prohibition in multi-
outdoor-unit
system)
Emergency
operation 2
(Setting for the
slave unit 1
39
operation
prohibition in multi-
outdoor-unit
system)
Emergency
operation 3
42
(prohibition of INV
compressor
operation)
Set-up of master /
51
slave units for multi
outdoor units
The numbers in the "No." column represent the number of times to press
the SET (BS2) button.
Description
<RTSYQ20P>
Prohibits operation of master unit.
Prohibits operation of slave unit.
Prohibits operation of inverter compressor of outdoor unit
or function unit.
Set up master and slave units for multi-connection
outdoor units.
After setting up, press the BS5 (REWIRING) button for 5
seconds or more.
SiBE31-801_C
Test Operation