E4" Outdoor Unit: Actuation Of Low Pressure Sensor - Daikin RTSQ20PY1 Service Manual

Vrv iii-c r-410a heat pump 50hz
Hide thumbs Also See for RTSQ20PY1:
Table of Contents

Advertisement

SiBE31-801_C
E4
4.16 "
" Outdoor Unit: Actuation of Low Pressure Sensor
E4
Remote
Controller
Display
Applicable
RTSQ8P~16P (Outdoor Unit)
Models
Method of
Abnormality is detected by the pressure value with the low pressure sensor.
Malfunction
Detection
Malfunction
Error is generated when the low pressure is dropped under compressor operation.
Operating pressure: 0.07MPa
Decision
Conditions
Supposed
Causes
Troubleshooting
Abnormal drop of low pressure (Lower than 0.07MPa)
Defect of low pressure sensor
Defect of outdoor unit PCB
Stop valve is not opened.
Clogged filter
Troubleshooting by Indication on the Remote Controller