SiBE31-801_C
<Function unit>
Elect.
Actuator
Symbol
Compressor
M1C
Electronic
expansion valve
Y1E
(Liquid injection)
Electronic
expansion valve
Y2E1
(Two-stage
selection 1)
Electronic
expansion valve
Y2E2
(Two-stage
selection 2)
Solenoid valve
Y1S
(Hot gas)
Solenoid valve
(Two-stage
Y2S
decompression)
Solenoid valve
Y3S
(Bypass 1)
Solenoid valve
Y4S
(Bypass 2)
Solenoid valve
(Liquid line
Y5S
selection)
Ending Conditions
<Indoor unit>
Part Name
Elect. symbol
Fan
M1F
Electronic
Y1E
expansion valve
Function
In preparation
Step 1
0 Hz
0 Hz
0 pls
0 pls
200 pls
0 pls
200 pls
0 pls
OFF
ON
OFF
OFF
ON
ON
ON
ON
ON
ON
or
170 sec.
Indoor unit actuator operation during defrost operation
Thermo. ON unit
Unit not in operation
Thermo. OFF unit
Thermo. ON unit
Unit not in operation
Thermo. OFF unit
In defrosting
operation
Step 2
210 Hz→52 Hz
0 pls
0 pls
0 pls
ON
OFF
ON
ON
ON
• After
• After a
a lapse
lapse
or
of 1 min.
of 12 min.
• Pc-Pe
• Tb>11°C
<0.5MPa
Special Control
After defrosting
operation
0 Hz
0 pls
200 pls
200 pls
OFF
OFF
ON
ON
ON
• After
a lapse
or
of 1 min.
• Pc-Pe
<0.5MPa
OFF
OFF
OFF
Defrost EV degree
256pls
Defrost EV degree
112