Daikin RTSQ20PY1 Service Manual page 57

Vrv iii-c r-410a heat pump 50hz
Hide thumbs Also See for RTSQ20PY1:
Table of Contents

Advertisement

SiBE31-801_C
Floor Standing Unit
1-2 ELECTRICAL SPECIFICATIONS
Power
Name
Supply
Phase
Frequency
Voltage
Current
Minimum circuit amps
(MCA)
Maximum fuse amps
(MFA)
Full load amps (FLA)
Voltage
Minimum
range
Maximum
Notes
Specifications
FXLQ20MAVE
FXLQ25MAVE
Hz
V
A
0.30
0.30
A
A
0.20
0.20
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
Maximum allowable voltage range variation between phases is 2%.
For more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books".
FXLQ32MAVE
FXLQ40MAVE
VE
1
50
220-240
0.60
0.60
15.00
0.50
0.50
-10%
+10%
above listed range limits.
MCA/MFA : MCA = 1.25 × FLA
MFA<= 4 × FLA
next lower standard fuse rating minimum 15A
select wire size based on the MCA
instead of a fuse, use a circuit breaker