Field Setting
<RTSYQ20PY1>
Cancel the disable-operation setting by each outdoor unit.
Make the following setting on the outdoor unit 1. (If this setting is made on an outdoor unit other
than the outdoor unit 2, the setting will become invalid.)
k Cancel disabling the outdoor unit 1 from operating:
Set No. 38 "Disable outdoor unit 1 operation" of setting mode 2 to "OFF".
k Cancel disabling the outdoor unit 2 from operating:
Set No. 39 "Disable-outdoor-unit-2 operation" of setting mode 2 to "OFF".
k Cancel disabling the outdoor unit 3 from operating:
Set No. 40 "Disable-outdoor-unit-3 operation" of setting mode 2 to "OFF".
<Function Unit>
Set the setting item No. 42 of "Setting mode 2" to "OFF".
Make the following setting with the function unit.
193
*It is possible to tell the outdoor units 1, 2, and 3 according the LED displays shown below.
LED display (
H1P-----------H7P H8P
h h k h h h h
Outdoor unit 1:
h h h h h h h
Outdoor unit 2:
h h h h h h h
Outdoor unit 3:
(Step)
(1) Press and hold the MODE button (BS1)
for 5 sec. or more.
(2) Press the SET button (BS2) 38 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
(Step)
(1) Press the MODE button (BS1) for 5
seconds or more.
(2) Press the SET button (BS2) 39 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
(Step)
(1) Press the MODE button (BS1) for 5
seconds or more.
(2) Press the SET button (BS2) 40 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
(Step)
(1) Press and hold the MODE button (BS1)
for a period of 5 sec. or more.
(2) Press the SET button (BS2) 42 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS2) once.
k
h
l
: ON
: OFF
: Blink)
k
l
h
(Factory setting)
LED display (
H1P-----------H7P
k h h h h h h
k k h h k k h
k h h h h l h
k h h h h h l
k h h h h h h
h h k h h h h
LED display (
H1P-----------H7P
k h h h h h h
k k h h k k k
k h h h h l h
k h h h h h l
k h h h h h h
h h k h h h h
LED display (
H1P-----------H7P
k h h h h h h
k k h k h h h
k h h h h l h
k h h h h h l
k h h h h h h
h h k h h h h
LED display (
H1P-----------H7P
k h h h h h h
k k h k h k h
k h h h h l h
k h h h h h l (Factory setting)
k h h h h h h
h h k h h h h
SiBE31-801_C
k
h
l
: ON
: OFF
: Blink)
(Factory setting)
k
h
l
: ON
: OFF
: Blink)
(Factory setting)
k
h
l
: ON
: OFF
: Blink)
(Factory setting)
k
h
l
: ON
: OFF
: Blink)
Test Operation