6.2.2 Compressor Step Control
Compressor operations vary with the following steps according to information in "6.2.1 Compressor PI Control".
RTSYQ10P
STEP
INV
STD
No.
1
52 Hz
OFF
2
56 Hz
OFF
3
62 Hz
OFF
4
68 Hz
OFF
5
74 Hz
OFF
6
80 Hz
OFF
7
88 Hz
OFF
8
96 Hz
OFF
9
104 Hz
OFF
10
110 Hz
OFF
11
116 Hz
OFF
12
124 Hz
OFF
13
132 Hz
OFF
14
144 Hz
OFF
15
158 Hz
OFF
16
166 Hz
OFF
17
176 Hz
OFF
18
188 Hz
OFF
19
202 Hz
OFF
20
210 Hz
OFF
21
52 Hz
ON
22
62 Hz
ON
23
68 Hz
ON
24
74 Hz
ON
25
80 Hz
ON
26
88 Hz
ON
27
96 Hz
ON
28
104 Hz
ON
29
116 Hz
ON
30
124 Hz
ON
31
132 Hz
ON
32
144 Hz
ON
33
158 Hz
ON
34
176 Hz
ON
35
188 Hz
ON
36
202 Hz
ON
37
210 Hz
ON
*1
38
218 Hz
ON
39
232 Hz
ON
40
248 Hz
ON
41
266 Hz
ON
*2
*1: Upper limit frequency for single-stage
compression
*2: Upper limit frequency for two-stage
compression in 50-Hz districts
Function
RTSYQ14 · 16P
STEP
INV
STD1
STD2
No.
1
52 Hz
OFF
OFF
2
56 Hz
OFF
OFF
3
62 Hz
OFF
OFF
4
68 Hz
OFF
OFF
5
74 Hz
OFF
OFF
6
80 Hz
OFF
OFF
7
88 Hz
OFF
OFF
8
96 Hz
OFF
OFF
9
104 Hz
OFF
OFF
10
110 Hz
OFF
OFF
11
116 Hz
OFF
OFF
12
124 Hz
OFF
OFF
13
132 Hz
OFF
OFF
14
144 Hz
OFF
OFF
15
158 Hz
OFF
OFF
16
166 Hz
OFF
OFF
17
176 Hz
OFF
OFF
18
188 Hz
OFF
OFF
19
202 Hz
OFF
OFF
20
210 Hz
OFF
OFF
21
52 Hz
ON
OFF
22
62 Hz
ON
OFF
23
68 Hz
ON
OFF
24
74 Hz
ON
OFF
25
80 Hz
ON
OFF
26
88 Hz
ON
OFF
27
96 Hz
ON
OFF
28
104 Hz
ON
OFF
29
116 Hz
ON
OFF
30
124 Hz
ON
OFF
31
132 Hz
ON
OFF
32
144 Hz
ON
OFF
33
158 Hz
ON
OFF
34
176 Hz
ON
OFF
35
188 Hz
ON
OFF
36
202 Hz
ON
OFF
37
210 Hz
ON
OFF
38
52 Hz
ON
ON
39
62 Hz
ON
ON
40
74 Hz
ON
ON
41
88 Hz
ON
ON
42
96 Hz
ON
ON
43
104 Hz
ON
ON
44
124 Hz
ON
ON
45
144 Hz
ON
ON
46
158 Hz
ON
ON
47
166 Hz
ON
ON
48
176 Hz
ON
ON
STEP
INV
STD1
STD2
No.
49
188 Hz
ON
ON
50
202 Hz
ON
ON
51
210 Hz
ON
ON
52
218 Hz
ON
ON
53
232 Hz
ON
ON
54
248 Hz
ON
ON
55
266 Hz
ON
ON
*1: Upper limit frequency for single-stage
compression in 50-Hz districts
*2: Upper limit frequency for two-stage
compression in 50-Hz districts
Normal Operation
*1
*2
92