A7" Indoor Unit: Malfunction Of Swing Flap Motor (M1S) - Daikin RTSQ20PY1 Service Manual

Vrv iii-c r-410a heat pump 50hz
Hide thumbs Also See for RTSQ20PY1:
Table of Contents

Advertisement

SiBE31-801_C
A7
4.5
"
" Indoor Unit: Malfunction of Swing Flap Motor (M1S)
A7
Remote
Controller
Display
Applicable
FXCQ, FXHQ, FXKQ
Models
Method of
Utilizes ON/OFF of the limit switch when the motor turns
Malfunction
Detection
Malfunction
When ON/OFF of the micro-switch for positioning cannot be reversed even though the swing
flap motor is energized for a specified amount of time (about 30 seconds).
Decision
Conditions
Supposed
Causes
Troubleshooting
Error code is displayed but the system operates continuously.
Defect of swing motor
Defect of connection cable (power supply and limit switch)
Defect of airflow direction adjusting flap-cam
Defect of indoor unit PCB
Troubleshooting by Indication on the Remote Controller