A9" Indoor Unit: Malfunction Of Electronic Expansion Valve Coil - Daikin RTSQ20PY1 Service Manual

Vrv iii-c r-410a heat pump 50hz
Hide thumbs Also See for RTSQ20PY1:
Table of Contents

Advertisement

SiBE31-801_C
A9
"
" Indoor Unit: Malfunction of Electronic Expansion
Valve Coil
A9
Remote
Controller
Display
Applicable
Indoor units except FXFQ models
Models
Method of
Check coil condition of electronic expansion valve by using micro-computer.
Malfunction
Detection
Malfunction
Pin input for electronic expansion valve coil is abnormal when initializing micro-computer.
Decision
Conditions
Supposed
Causes
Troubleshooting
Defective drive of electronic expansion valve
Defective PCB of indoor unit
Defective relay cables
Troubleshooting by Indication on the Remote Controller