3.2.5 Cool / Heat Mode Switching
There are the following 4 cool/heat switching modes.
(1) Set Cool / Heat Separately for Each Outdoor Unit System by Indoor Unit Remote Controller
<Set the master unit (= indoor unit having the right to
select the cooling/heating operation mode).>
In the case of wired remote controllers
• After the check operation, "CHANGEOVER UNDER
CONTROL" is flashing in all connected remote controllers.
• Select an indoor unit to be used as the master unit in
accordance with the request from the customer.
(It is recommended to select an indoor unit which will be
used most often as the master unit.)
• Press the operation mode selector button in the remote
controller of the indoor unit selected as the master unit.
• In that remote controller, "CHANGEOVER UNDER
CONTROL" disappears. That remote controller will control
changeover of the cooling/heating operation mode.
• In other remote controllers, "CHANGEOVER UNDER
CONTROL" lights.
For the details, refer to the installation manual
supplied together with the indoor unit.
Test Operation
Set cool/heat separately for each outdoor unit system by indoor unit remote controller.
Set cool/heat separately for each outdoor unit system by cool/heat selector.
Set cool/heat for more than one outdoor unit system simultaneously in accordance with
unified master outdoor unit by indoor unit remote controller.
Set cool/heat for more than one outdoor unit system simultaneously in accordance with
unified master outdoor unit by cool/heat switching remote controller.
It does not matter whether or not there is outdoor - outdoor unit wiring.
Set outdoor unit PCB DS1-1 to IN (factory setting).
Set cool/heat switching to IND (individual) for "Setting mode 1" (factory setting).
Set the master unit (= indoor unit having the right to select the cooling/heating operation
mode).
Indoor unit
P1P2
Remote
controller
C/H SELECT
TEST
MODE
IND MASTER SLAVE
MALFNC.
H1P
H2P
H3P
H4P
H5P
C/H SELECT
OUT
O
Dip SW.
DS1-1
IN
I
C/H SELECTOR
I-O
A
B
C
F1
F2
F1
F1 • F2
F1 • F2
Indoor unit
P1P2
Remote
controller
In the case of wireless remote controllers
• After the check operation, the timer lamp is flashing in all
connected indoor units.
• Select an indoor unit to be used as the master unit in
accordance with the request from the customer.
(It is recommended to select an indoor unit which will be
used most often as the master unit.)
• Press the operation selector mode button in the remote
controller of the indoor unit selected as the master unit. A
"peep" sound is emitted, and the timer lamp turns off in all
indoor units.
• That indoor unit will control changeover of the cooling/
heating operation mode.
L.N.O.P. DEMAND
H6P
H7P
O-O
OUT-MULTI
F2
Q1
Q2
Field Setting
178