SiBE31-801_C
<Indoor Units>
Part Name
Elect. symbol
Fan
M1F
Electronic
Y1E
expansion valve
Function
Indoor unit actuator operation during cooling oil return operation
Thermo. ON unit
Unit not in operation
Thermo. OFF unit
Thermo. ON unit
Unit not in operation
Thermo. OFF unit
Remote controller setting
OFF
Remote controller setting
Normal opening degree
Normal opening degree for forced thermostat ON
224 pls
Special Control
108