7. Troubleshooting (Heat Reclaim Ventilation)

60
7.1
"
" Error of External Protection Device
Remote
Error Code
Controller LCD
Display
Applicable
Heat reclaim ventilation
Models
Method of
Detect abnormal output from the external safety device with contact input (between J1 and JC).
Malfunction
Detection
Malfunction
Abnormal output (short circuit) signal is issued from the external safety device.
Decision
Conditions
Supposed
Causes
Troubleshooting
Troubleshooting
60
Inspection OFF Unit No. Blinking
Activation of external safety device
Faulty connection of the abnormal output signal line
Short circuit established in the abnormal output signal line
Faulty control PCB
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Is the signal line properly
connected to the terminals
of J1 and JC connectors,
respectively?
YES
Is the voltage between
the terminals of J1 and
JC connectors 0V?
YES
Disconnect the signal line
from the terminals of J1 and
JC connectors, respectively.
Is the voltage between
the terminals of J1 and
JC connectors 0V?
NO (Approx. 16V)
Disconnect the signal line
from the external safety
device.
Make measurement of
resistance between two
wires of the signal line using
a multiple meter.
Several MΩ to infinite Ω

Troubleshooting (Heat Reclaim Ventilation)

NO
NO (Approx. 16V)
YES
0 to several tens of kΩ
Properly connect signal line to the
terminals of J1 and JC connectors,
respectively.
Replace the control PCB.
Replace the control PCB.
Replace the signal line.
Malfunction of external safety device.
*The PCB is normal.