Troubleshooting by Indication on the Remote Controller
C5
4.10 "
" Indoor Unit: Malfunction of Thermistor (R3T) for
Gas Pipes
C5
Remote
Controller
Display
Applicable
All indoor unit models
Models
Method of
Malfunction detection is carried out by temperature detected by gas pipe thermistor.
Malfunction
Detection
Malfunction
When the gas pipe thermistor becomes disconnected or shorted while the unit is running.
Decision
Conditions
Supposed
Causes
Troubleshooting
∗
239
Defect of indoor unit thermistor (R3T) for gas pipe
Defect of indoor unit PCB
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Remove the thermistor from
the indoor unit PCB, and then
insert it again.
Is the thermistor
normal?
NO
Remove the thermistor from the
indoor unit PCB, and then make
resistance measurement of the
thermistor using a multiple
meter.
*
5 kΩ to 90 kΩ
YES
Refer to "Thermistor Resistance / Temperature Characteristics" table on P.408.
YES
NO
SiBE31-801_C
Normal (The malfunction is caused
by faulty contact.)
Replace the thermistor (R3T).
Replace the indoor unit PCB.
Troubleshooting