Daikin RTSQ20PY1 Service Manual page 17

Vrv iii-c r-410a heat pump 50hz
Hide thumbs Also See for RTSQ20PY1:
Table of Contents

Advertisement

SiBE31-801_C
Indoor unit capacity
New refrigerant model code
Selecting model capacity
Equivalent output
Use the above tables to determine the capacities of indoor units to be connected. Make sure the
total capacity of indoor units connected to each outdoor unit is within the specified value (kW).
General Information
P20
P25
P32
type
type
type
type
2.2
2.8
3.5
kW
kW
kW
0.8HP
1HP
1.25HP 1.6HP 2.0HP 2.5HP 3.2HP
The total capacity of connected indoor units must be within a range of 50 to 130% of the
rated capacity of the outdoor unit.
In some models, it is not possible to connect the maximum number of connectable indoor
units. Select models so the total capacity of connected indoor units conforms to the
specification.
P40
P50
P63
P80
type
type
type
4.5
5.6
7.0
9.0
kW
kW
kW
kW
Model Selection
P100
P125
P140
P200
type
type
type
type
11.2
14.0
16.0
22.4
kW
kW
kW
kW
4HP
5HP
6HP
8HP
P250
type
28.0
kW
10HP